You might also like
INPUT: 24 V DC (SELV/PELV)
OUTPUT: max. 2× 20/1× 40 A
OUTPUT: max. 2× 20/1× 40 A
General data
Standards | EN 61000-6-2, EN 61000-6-3 |
---|---|
Bridging concept | two sides, with spring clamp terminals or bridge set (max. 40 A) |
Relative humidity | 5...95%, no condensation |
Power loss | U (approx. 0.5 V) ×I |
Efficiency | 97% |
Connection | Spring clamp terminals |
Mounting method | DIN-rail mountable TH35 (EN 60715) |
Temperature range | -25...+55 °C (storage temperature -25...+85 °C) |
Output
Output voltage | 24 V DC (21...30 V DC) |
---|---|
Output current | 20 A (-25...+55 °C); 40 A (-25...+40 °C) |
Overload | at 20 A +50% for 4 s |
LED display | LED (green) |
Alarm output | potential free per channel (relay contact) |
Input
Input voltage | 24 V DC (21...30 V DC) |
---|---|
Input current | 2× 20/1× 40 A |
Total current | max. 40 A |
Invers-polarity protection | internal protection against reverse polarization up to 60 V DC |
Auto-Balancing (50/50) | no |
Commercial data
country of origin | CZ |
---|---|
customs tariff number | 85411000 |
EAN | 4048879079884 |
eClass | 27049002 |
Packaging unit | 1 |