Do you have any questions about our products? Our experts will be glad to assist you! Just give us a call 770-497-9292
Zoom
EMPARRO67 HYBRID POWER SUPPLY 1-PHASE, 2-CHANNELS
Product may differ from image

EMPARRO67 HYBRID POWER SUPPLY 1-PHASE, 2-CHANNELS

IN: 100-240VAC OUT: 24VDC/MAX. 10A (1-8/CHANNEL)
Art.No.: 85678
Weight: 1.85 kg
 Product Comparison

You might also like

Emparro®67 Hybrid
2× MICO M12 IOL
M12 (female) 5-pole, L-coded
Current: 10 A
INPUT: 90...265 V AC/90...265 V DC
OUTPUT: 24...28 V DC
Preventive Diagnostic
Over current protection device
controllable via IO-Link
Input
Input voltage 90...265 V AC/90...265 V DC
Input current 1.2 A (240 V AC)
Inrush current after 1 ms max. 5.9 A  (230 V AC)
Power factor 0.88 (230 V AC)
Connection 7/8" (male), 3-pole
Frequency 50...60 Hz
Input fuse (internal) 6.3 A (T)
General data
Standards EN 60950-1, EN 61204-3, EN 55022 B, EN 61000-3-2
Relative humidity 4...100%
Protection IP67
Efficiency 91.6% (115 V AC); 92.8% (230 V AC)
MTBF 430 000 h
Mounting method 6 hole screw mounting
Dimensions H×W×D 216×110×53 mm
Temperature range -25...+50 °C, ...+80 °C derating (storage temperature -25...+85 °C)
Output
Output voltage 24 V DC (SELV), ±1%; 24...28 V adjustable
Output current max. 8 A (per channel), max. 10 A (total)
No. of channels 2× MICO (Over current protection device)
Connection M12 (female) 5-pole, L-coded
Mains failure bridging time min. 20 ms (230 V AC)
Ripple max. 10 mV eff/rms
Spikes max. 150 mV ss/pp
Unit protection Short-circuit, overload and temperature
LED display LED (green): OK; LED (red): overload, overheating or short-circuit
Parallel usage/serial usage no
Commercial data
country of origin CZ
customs tariff number 85044090
EAN 4048879798433
Packaging unit 1
 
Data Regarding Article:
  • Download Data Sheet
  • Download Approvals and certificates 85678_-NMTR7_ulc_z_a.pdf
  • Download Approvals and certificates 85678_E200364-NMTR_ul_z_a.pdf
  • Download Approvals and certificates 85678_24-06.19_ce_z_a.pdf
  • Download China RoHS information EPUP-25_CHR_x_1.pdf
  • Download Configuration Files 85678_kfg_e_23.zip
  • Download Drawing Files 85678_stp_x_a.zip
  • Download Drawing Files 85678_dxf_x_a.zip
  • Download Drawing Files 85678_p8_2_80.zip
  • Download Installation Instructions 85679_ina_10_10.pdf
  • Download Product data 85678_pd_x_10.zip
cULus
IO-Link